This is typically accomplished via a shunt trip device. Be sure to provide a horn/strobe alarm in large equipment rooms because they can be noisy, isolated places. The electrical conductors and equipment for non-mine elevators that extend below grade are under NEC jurisdiction. (ASME has a separate document, A18.1-2008 Safety Standard for Platform Lifts and Stairway Lifts). The traveling cable or raceway is also permitted to include shielded conductors and/or one or more coaxial cables. A single means for disconnecting all ungrounded main power-supply conductors is required and must be designed so no pole can be operated independently. All rights reserved. All equipment in a machine room-less design is installed within the elevator shaft or exterior compartment near the elevator shaft, including the elevator controller and the elevator disconnecting means. High-rise buildings pose additional concerns. Because of this, there is often a communications gap between the electrical system designer, whose design typically stops at the required elevator disconnecting means, and the architect who designs the elevator system. Section 620.85, GFCI Protection for Personnel, provides that 125-V, single-phase, 15- and 20-amp receptacles installed in pits, hoistways, machinery spaces, machine rooms, escalators and moving walks, and on elevator car tops are to be GFCIs. 3. Sign up for our free e-newsletter. Society of Mechanical Engineers. (g) Stop Switch in Pits. Some elevator controller manufacturers believe this is an issue for the electrical system designer and installer to address and remedy by adding impedance to the system for lowering the available fault current. Many of these are for portable lighting.). Within cars, these additional wiring methods are permitted: The following additional wiring methods are permitted on the car assembly in lengths not exceeding 6 ft.: Within machine rooms, these additional wiring methods are permitted: The following wiring methods are permitted on the counterweight assembly in lengths not to exceed 6 ft.: Having looked at NEC 2011 mandates for elevator and related equipment installations, we will cover wiring methods, overcurrent protection, grounding and other related NEC provisions in part two of this series , running in the April 2012 issue of ELEVATOR WORLD. The sump pump/drain shall have the capacity to remove a minimum of 11.4 m. 3 /h (3,000 gal/h) per elevator. Flexible cords and cables part of listed equipment operating at 30 V (42 VDC) or less, similarly supported and protected, jacketed and flame retardant, are permitted. -inch conduit is needed to the sump pump. He participates in IEEE (Senior Member) with Industrial and Commercial Power Systems, NEMA (member of the Codes & Standards Committee), NFPA (committee member for NEC CMP-13 and NFPA 79), UL (508/60947 and 508A) and IAEI activities. NEC 620.62 requires the elevator disconnecting means (fused switch or circuit breaker) to selectively coordinate with all supply-side overcurrent devices. Fuses: Verify that the correct size, type and capacity are installed. We shall now take a look at the principle requirements of Article 620, with particular emphasis on wiring requirements for elevator shafts, machine rooms and cars. If you can illuminate the pit using lights that are "above the top of the pit" (whatever that . But by understanding how these items fit together and what purpose they serve, you can have a successful project. NEC Guidelines on Commercial Garages. Related Code Sections 802.1.8 Indirect/Special Waste, Elevator Pit Drain or Sump Pump +91 8025357028, 2022 Elevator World, LLC. Hint: Duct Tape to the Rescue, NEC: Air Conditioning and Refrigerating Equipment Part 5. , !! This will normally require you to vent the room with a fire/smoke damper and include smoke detector signals in the control logic. Part IX, Grounding, states that metal raceways, Type MC cable, Type MI cable or Type AC cable attached to elevator cars are to be bonded to metal parts of the car bonded to the equipment grounding conductor. Utility-owned electrical structures not directly concerned with electrical generation, transmission and distribution are NEC regulated. There are options available to achieve this depending upon the customers needs. Hard-service cords are permitted only as flexible connections for the top-of-car operating device or the car-top work light. If your specifications require a vent at the top of the shaft for venting smoke, you must provide a key switch with a pilot light to control that vent. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciation. NEC specifies Hoistway wiring, and doesn't seem to distinguish between hoistway and pit. Traction elevators raise and lower the elevator cab with cables, a pulley system, and counter weights powered by a motor at the main drive wheel. This is important as the tradition of using only time-current curves for the analysis of overcurrent device operation is usually not sufficient since the time-current curves traditionally stop at 0.01 second (not time zero). The cover shall be secured and level with the pit floor. A surge of immigration to the U.S., the end of slavery and, on both sides of the Atlantic Ocean, a burgeoning industrial revolution ignited an acceleration in new building. Bonding of elevator rails to a lightning-protection system grounding conductor is permitted, but the conductor itself is not to be located in the hoistway. The light switch in the pit must be mounted 42 in. NFPA 72 requires the control circuit between the Fire Alarm System and the shunt trip be monitored for integrity. Besides the power-supply disconnect discussed, it is provided that elevators have a single means for disconnecting all ungrounded car lights, receptacles and ventilation power-supply conductors for that elevator car. 988 0 obj
<>stream
The article stands apart from the rest of the code in the sense it exempts these categories of circuits from the general requirements for wiring in most occupancies, found in Chapter 3. You'll be responsible for specifying the items related to the fire alarm and some controls, as well as supplying lighting and power to the equipment room and elevator pit. 4.0 (2 Reviews) (2) CLAIMED . Apr 24, 2013. correct me if I'm wrong, but I believe it's damp. The code is not concerned with the efficiency or sophistication of equipment that it covers, except insofar as safety (in terms of human injury and property damage) is concerned. Conductors supplying more than one motor, motor controller or power transformer are to have an ampacity not less than the sum of the nameplate current ratings of the equipment plus all other connected loads. With heavy use on a hot day, the oil can overheat, causing elevator shutdown. The demand factors are given in Table 620.14, which allows significant reductions as the number of motors is increased. Additional requirements concern escape routes. 354 Morgan Ave. Here, the National Electrical Safety Code has jurisdiction. 2.2.2.6 . Of particular importance is the location of the disconnecting means so it can be found by an individual who may not be familiar with the installation. You'll need to run telephone cables to the equipment room control panel, but the elevator supplier will take care of getting the cables to the elevator cab. Other requirements: Spa's and Hot Tubs 1996 NEC 15-20 Amp 120 volt Receptacle Requirements for Dwelling units: All outdoor The basic requirement is for minimum clear distances of various depths for equipment operating at 600 V or less, nominal, depending upon voltage to ground and lateral distance to insulated or grounded surfaces or exposed live parts (not an issue in elevator machine rooms). Other codes and standards interact with the NEC, and it is necessary to see how they all work together in order to create safe and compliant elevator designs/installations. The surest means of avoiding an arc-flash hazard is to lockout and tagout the electrical service to a controller. It does specify wiring methods allowed, though, in 620. CLAIMED . These circuit breaker selective coordination tables can be used to identify the maximum fault current that a pair of circuit breakers can selectively coordinate. It is also essential that machine-room lighting be totally reliable and separate from the machinery supply to facilitate troubleshooting in the event of elevator problems. Each of these performs a different function, and the wiring mandates vary accordingly. This equipment is restricted to that used in connection with the specific elevator, dumbwaiter, escalator, moving walk, platform lift or stairway chairlift. Required lighting shall not be connected to the load side of a ground-fault circuit interrupter. A few years later, in 1880, Werner von Siemens built the first electric elevator, setting the stage for a new industry that would change the world by making the practical use of tall buildings possible. Article 620s Definitions section includes two terms that describe spaces not attached to the outside of a hoistway. A traction elevator's equipment room is typically located at the top of the building, directly over or adjacent to the shaft. The electrical system designer calculates the maximum available fault current at the elevator controller. Part VIII, Machine Rooms, Control Rooms, Machinery Spaces, and Control Spaces, states elevator and similar-installation driving machines, motor-generator sets, motor controllers and disconnecting means are to be installed in a room or space set aside for that purpose. Elevators with driving machines located on the car or counterweight, or in the hoistway are permitted outside the specified spaces. If the smoke detector at the designated landing goes into alarm, the elevator will stop at a predetermined alternate floor, which is usually the floor above the designated floor. Though I understand how someone might argue two. In these installations, it is best to design the elevator controller so the elevator controller SCCR is adequate for the available fault current. NEC 2011 Article 620.21(2)(b) states that hard-service cords and junior hard-service cords that conform to the requirements of Article 400 (Table 400.4) are permitted as flexible connections between the fixed wiring on the car and devices on the car doors or gates. endstream
endobj
startxref
Years may lapse between the design and installation stages of a project. Many people use portable generators until power is restored. Liquid-tight flexible nonmetallic conduit, Flexible cords and cables, or conductors grouped together and taped or corded, are permitted without raceway, where they are part of listed equipment, a driving machine or a driving-machine brake, Flexible metal conduit, liquid-tight flexible metal or nonmetallic conduit, 3/8 in. If you specify a rescuvator, you must also specify a disconnect switch with an auxiliary contact that opens when the disconnect arm moves to the open position, but stays closed when the OCPD trips. The usual scenario for electrical injury is shock when electrical current passes through the human body. Flexible cords and cables (same conditions as within hoistways). If we fast forward more than 36 centuries, we see some important new developments in elevator technology. If you provide your elevators with emergency power, you must run communications wires between the automatic transfer switch (ATS) and the elevator control panel. In Part One of this series (ELEVATOR WORLD, April 2012), we began an examination of National Electrical Code (NEC) 2011 mandates for elevators and related equipment installations. First, the ATS signals the elevators that it's about to switch over to emergency power preferably 30 sec or more prior to switching, which allows the elevator controller to bring each elevator cab to the nearest landing and stop, thus protecting the motors and electrical system. NEC 2011 also addresses branch circuits for machine room or control room/machinery space or control-space lighting and receptacles. Many undertake trips in these devices two or more times daily in full confidence that they will survive an uneventful experience with a minute chance of disaster or even inconvenience. In elevators provided with Firefighters' Emergency Operation, a drain or sump pump shall be provided. Per the 2017 NEC, if the elevator is designated as an emergency system load, the disconnect must be protected by a surge protective device (SPD). IAEI News Magazine. (To design and install an elevator for a Class I, Division 1 location would be quite an undertaking.). Motor controllers are permitted outside the spaces specified above. Requirements for commercial garages per the National Electrical Code. Follow the manufacturers instructions and precautions. Otherwise, specify that the elevator supplier provide a battery back-up unit to power the lights in the event of an outage. David Herres holds a New Hampshire Master Electricians license and has worked as an electrician in the northern part of that state for many years. Part II of Article 620 concerns conductors used in elevator work, and several important requirements are covered. 2. For elevators that regenerate power back into a power source unable to absorb the regenerative power under overhauling elevator load conditions, a means to absorb this power is to be provided. The various items to consider and check when designing for elevator installations have many potential pitfalls. Get more of Elevator World. (e) Pit Maintenance. These are the principle NEC 2011 Article 620 mandates. In fact, an entire elevator system for a project is most often designed and specified by the architect who has little understanding of the electrical distribution system. This is the area within the hoistway beneath the car, and there are occasions when elevator technicians have to work in this area for maintenance and troubleshooting. The locking capability is important so during maintenance, the equipment will not be inadvertently energized. (C) Duplex Receptacle. It is further stated that the disconnecting means are not to disconnect the branch circuits required in sections 620.22, 620.23 and 620.24. As mentioned, traditional installations of a traction or hydraulic elevator include a separate machine room. Upon loss of power, the rescuvator controls the cab, lowers it to the designated floor, and opens its doors. ) > word/_rels/document.xml.rels ( N0HC;qRN/W$#{1EM]ZY|vj5h),-g!`./V/KKFY4D#la&V#=$Q7|l/d#hS 7+IDZ!J 6KucD^s`+>=(3E The basic wiring methods are rigid-metal, rigid nonmetallic or intermediate-metal conduit; electrical metallic or rigid nonmetallic tubing; wireways; or Type MC, MI or AC cable, unless otherwise permitted. from the exposed components, and the incident energy calculated at 18 in. It is important to note, that these selective coordination tables can indicate a lack of selective coordination at a given fault current for circuit breakers that do not show overlap on the time-current curves of the circuit breakers. (B) Lighting Switch. hb``` ea``j~p2nfH
'xXg00,/(_ Iq8PDdg-~ s$!XI;Fn0vu
`h`R 1y
0B.":9.@, e`xI;=7O3fvbb8:SC;%O*20] David Herres The branch circuit is to be protected by an overcurrent device located in the machine room, control room/machinery space or control space. You can email the site owner to let them know you were blocked. You must locate this key switch at the main lobby or at the building fire command center. z!0: - [Content_Types].xml ( n0EUb*>-RxV=QUAl"93dFk%Y?l}MGDV Also located in this room might be, but not limited to: exhaust fan, cooling unit (depending on local requirements and/or requirements set forth by the individual elevator supplier), lighting, voice and/or data drop serving the elevator cab emergency phone, elevator controller primary fused disconnect, elevator feeder shunt-trip circuit (i.e., shunt-trip circuit breaker), elevator cab lighting fused switch, and convenience receptacle(s). above the seal plate, adjacent to the ladder. Selective coordination is defined by the NEC as: Localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the selection and installation of overcurrent protective devices and their ratings or settings for the full range of available overcurrents, from overload to the maximum available fault current, and for the full range of overcurrent protective device opening times associated with those overcurrents.. It is important for the design engineer to coordinate with the architect to determine the elevator manufacturer basis of design to determine if and when additional power and lighting is required. They are to be located so as to be protected from physical damage, are to be of a flame-retardant type, and must be part of listed equipment, a driving machine or a driving-machine brake. The branch circuit supplying these units is to be similarly dedicated, with the associated overcurrent device located in the machine room or similar location. Flexible metal, liquid-tight flexible metal or liquid-tight flexible nonmetallic conduit 3/8 in. Overload protection for motors is to conform with Article 430, Part III, the general code area that covers motor and branch-circuit overload protection for all motors. However, space is frequently limited within the shaft and as such many ancillary components (shunt trip circuit breakers, fused disconnects) may need to be located outside of the elevator shaft. The thinking behind this requirement is that the injured worker could have severe hand burns and be unable to operate a conventional doorknob. This website is using a security service to protect itself from online attacks. Article 511 provides the requirements for commercial garages areas used for the storage or repair of self-propelled vehicles that use combustibles (liquid or gas) for power. As for height, the working space must extend from the grade, floor or platform to 6-1/2 ft. or the height of the equipment, whichever is greater. If elevators are supplied by the emergency, legally required standby or critical operation power systems, then selective coordination is required per the 2017 NEC in 700.32, 701.27 or 708.54. Proper selective coordination in a multi-elevator installation on the same feeder ensures if one elevator develops a fault, the other units will not be shut down. NEC has a further note that the term wheelchair lift has been changed to platform lift.. ASME A17.1 . A second door is required if the equipment is rated over 1200 amps and over 6 ft. wide. NEC articles generally adhere to a template, which greatly aids in navigating and quickly locating mandates as needed for project design or, on an installation level, in the field. Building codes were deemed necessary to protect the public against shoddy builders and outmoded construction techniques. Additionally, ampacities of the individual conductors and flame-retardant properties of the overall cable are important factors. After reading this article, you should have learned: Which locations require sepa-rate, dedicated branch circuits Which branch circuits are not to be provided with ground fault circuit interrupter (GFCI) pro-tection Which locations must have one or more duplex receptacles Where overcurrent protection for hoistway, pit and machine-room lighting must be located How unsupported lengths of traveling cables are measured. However, when I've put in elevators, NEC seems to always take a back seat to ANSI, which seems . This clear working space must be 30 in. He also required GFCI protection for the hard-wired sump pump that did not require it. (Cross-sectional areas of conductors are given in Chapter 9, Tables 5 through 8. This requirement applies to all controllers, disconnecting means and other electrical equipment that may need servicing, inspection or maintenance. 974 0 obj
<>/Filter/FlateDecode/ID[<64E135C225F1064D91BC8119D14516A9>]/Index[953 36]/Info 952 0 R/Length 105/Prev 204101/Root 954 0 R/Size 989/Type/XRef/W[1 3 1]>>stream
Where multiple driving machines are connected to a single elevator, there is to be one disconnecting means to disconnect the motor(s) and control-valve-operating magnets. Part VII, Overcurrent Protection, divides this topic into four categories for elevators and similar equipment, depending upon the nature of the specific equipment: For operating devices and control and signaling circuits, protection against overcurrent is in accordance with the requirements of Sections 725.43 and 725.45. Depending on your local codes, you can do this by installing heat or smoke detectors within 24 in. Always verify all conditions and requirements with the state and the AHJ where the installation is taking place. It is conditionally provided that fiber-optic cables and conductors for operating devices, operation and motion control, power, signaling, fire alarm, lighting, heating and air-conditioning circuits of 600 V or less are permitted to be run in the same traveling cable or raceway system. For example, an inadequately supported ceiling fan could fall and cause injury or property damage. NEC Article 620 Part IV, Installation of Conductors, contains key mandates for elevator wiring. It is further stipulated that internal voltages of power-conversion equipment and functionally associated equipment, and the operating voltages of wiring interconnecting the equipment, are permitted to be higher, provided that the equipment and wiring are listed for the higher voltages. The hazards are external to the equipment enclosure since equipment SCCR testing and evaluation criteria for product standards are most often performed with the enclosure doors closed and latched, and the fault occurring external to the enclosure. 6 Stop Switch in Pits There shall be installed in the pit of each elevator an ASME A17.1 CODE enclosed stop switch or switches meeting the requirements The following material is reprinted with permission from the American of 2.26.2.7 and 2.2.6.1 through 2.2.6.3. (A) Separate Branch Circuit. The floor specified as the designated landing, which must be approved by the Fire Marshal, is usually the floor on grade level so passengers can quickly exit to the outside.
These are covered for generic, non-elevator specific use in earlier articles, 376 and 378, in Chapter 3, Wiring Methods and Materials. The NEC rule specifies that the minimum size for paralleled conductors is 1/0 AWG, which is much too big for an elevator traveling cable. A little more narrowly focused (yet of great consequence) is the ubiquitous NEC, which, in the National Fire Protection Association (NFPA)s venerable Handbook edition, devotes 18 double-column pages to electrical design and installation requirements for elevators, escalators and related equipment. The elevator controller manufacturer must determine the required elevator controller SCCR as stated in the elevator controller specification and provide an elevator controller SCCR that is equal to or greater than the available fault current thats indicated in the design documents where there are multiple elevator controllers at different locations. The code exempts some fairly broad areas where compliance is not expected.
Why Did Big Al And Charlie Get Fired, Sistina Giordano Marriage, Essential Oils For Idiopathic Guttate Hypomelanosis, Guardian Life Health Insurance Contact Number, Miniature Schnauzer Puppies For Sale In Springfield, Il, Articles N
Why Did Big Al And Charlie Get Fired, Sistina Giordano Marriage, Essential Oils For Idiopathic Guttate Hypomelanosis, Guardian Life Health Insurance Contact Number, Miniature Schnauzer Puppies For Sale In Springfield, Il, Articles N